3 Phase
Power Distribution Transformer
After
numerous further conversions in the transmission
and distribution network the 3 phase power is
finally transformed to the standard mains voltage (the
voltage of "house" or "household"
current in American English). The power may already
have been split into single phase at this point or it
may still be 3 phase. Where the step-down
is 3 phase, the output of this transformer
is usually star connected with the standard mains
voltage (120V in North America and 230V in Europe)
being the phase-neutral voltage.
Another
system commonly seen in the USA is to have a delta
connected secondary on the step
down transformer with a center tap on one of the
windings supplying the ground and neutral. This allows
for 240V 3 phase as well as three different single
phase voltages (120V between two of the phases and the
neutral, 208V between the third phase (sometimes known
as a wild leg) and neutral and 240V between any two
phases) to be made available from the same supply.
Generating
3 Phase Power From Single Phase
When
single phase power is readily available but 3-phase
power is not already allocated, there is an easy way
to generate 3 phase power with a 3 phase power
generating Rotary Phase Converter or with a modern
Motor Generator Set. Today these are a super efficient
method to get 3 phase power anywhere single phase is
already available. Read more about super
efficient 3 phase generating Rotary
Phase Converters here.
Electric Power Distribution History
In
the early days of electricity
generation, direct
current (DC)
generators would be connected to loads at the same voltage.
The generation, transmission and loads all needed to
be of the same voltage because, at the time, there was
not a common way of doing DC voltage conversion (other
than motor-generator sets which today have became
super efficient). The voltages usually had to be
fairly low with old generation systems due to the
difficulty and danger of distributing high voltages to
small loads. The losses in a line transmission cable
are proportional to the square of the current, the
length of the cable, and the resistive nature of the
conductor line wire material, and are inversely
proportional to cross-sectional area. Early power
transmission networks were already using copper, which
is one of the best conductors that is also very
economically feasible for this application. To reduce
the current while keeping power transmission constant
requires increasing the voltage which, as previously
mentioned, was, at that time, problematic. This meant
in order to keep losses to a reasonable level the (DC)
Edison power transmission system needed thick cables
and local power generators.
Alternating
Current (AC) Becomes Most Common Standard
Soon, the adoption of alternating
current (AC) for electricity
generation
dramatically changed the situation. Power
transformers,
installed at power
substations,
could be used to raise the voltage from the generators
and reduce it to supply loads. Increasing the voltage
reduced the current in the power transmission and
distribution lines. Thus the size of conductors
required and distribution losses incurred were also
reduced. This made it more economic to distribute
power over long distances. The ability to transform to
extra-high voltages enabled power
generators to be located far from loads with
transmission systems to interconnect generating
stations and distribution networks.
Though
due to power line losses, it is still often valuable
to locate the power generators nearby the actual power
load.
In
North America, the early power distribution systems
used a voltage of 2200 volts corner-grounded
delta. Over time, this was gradually increased
to 2400 volts. As cities grew, most 2400 volt systems
were upgraded to 2400/4160 Y
three-phase systems, which also benefited from
better surge suppression due to the grounded neutral.
Some city and suburban power distribution systems
continue to use this range of voltages, but most have
been converted to 7200/12470Y.
European
systems used higher voltages, generally 3300 volts to
ground, in support of the 220/380Y volt power systems
used in those countries. In the UK, urban power
generation and transmission systems progressed to 6.6
kV and then upgraded to 11 kV (phase to phase), the
most common power distribution voltage.
North
American and European power distribution systems also
differ in that North American power distribution
systems tend to have a greater number of low-voltage step-down
transformers located closer to customers'
premises. For example, in the US a pole-mounted
transformer in a suburban area may supply only one
or a very few houses or small businesses, whereas in
the UK a typical urban or suburban low-voltage
substation might be rated at 2MW
of power and supply a whole neighborhood. This is
because the higher voltage used in Europe (230V vs
120V) may be carried over a greater distance without
an unacceptable power loss. An advantage of the North
American setup is that failure or maintenance on a
single power transformer will only affect a few
customers. Advantages of the UK setup are that fewer
transformers are required; larger and more efficient
transformers are used, and due to diversity there need
be less spare capacity in the transformers, reducing
power wastage.
Rural
power electrification systems, in contrast to
urban power systems, tend to use higher voltages
because of the longer distances covered by those power
distribution lines. 7200 volts is commonly used in the
United States; 11kV and 33kV are common in the UK, New
Zealand and Australia; 11kV and 22kV are common in
South Africa. Other voltages are occasionally used in
unusual situations or where a local utility simply has
engineering practices that differ from the normal
practices
Power
Distribution
Network Layout
Power distribution
networks are typically arranged out in one of two
types, radial or interconnected. A radial network
leaves the station and passes through the network area
with no connection to any other supply. This is
typical of long rural lines with isolated load areas.
An interconnected network is generally found in more
urban areas and will have multiple connections to
other points of supply.
These
points of connection are normally open but allow
various configurations by closing and opening
switches. The benefit of the interconnected model is
that in the event of a fault
or required maintenance a small area of network can be
isolated and the remainder kept on supply. The
only downside to this design occurs when there is a major
power outage that causes a domino effect damaging the
power supply systems from the whole network leaving
more customers without power. There are
protections in place to keep this from happening
though it still occurs every few years in places where
this method of power distribution and transmission is
used.
Characteristics
of the supply given to customers are generally
mandated by law
and by contract
between the electric power supplier and customer.
Variables include:
AC
or DC
- Virtually all public electricity supplies are AC
today. Users of large amounts of DC power such as some
electric
railways, telephone
exchanges and industrial processes such as aluminum
smelting either operate their own generating equipment
or have equipment to derive DC from the public AC
supply).
Phase
and Frequency Converters
There
are several instances where the equipment may need not
only the phase changed from 1-phase, or the rare
2-phase (in the US this is mostly used in Chicago) to
3 phase power, but also the frequency
converted from 50Hz to 60Hz or 400Hz (400Hz is
mostly used in ships and aircraft). Click here
to read more about 3
phase frequency converters.
Continue
And Read About Additional 3 Phase Power Details: